Cyber Risks · Unit 42 Palo Alto Networks

Privileged File System Vulnerability Present in a SCADA System

Summary: Unit 42 found CVE-2025-0921, a privileged file system operations vulnerability with a Medium CVSS score of 6.5, in the Iconics Suite SCADA system for Microsoft Windows versions 10.97.2 and earlier, identified during an early 2024 assessment that surfaced five vulnerabilities. A non-administrative attacker can chain it with CVE-2024-7587, which gives every local user read and write access to C:\ProgramData\ICONICS, to point the Pager Agent's SMSLogFile path at a symbolic link targeting C:\Windows\System32\cng.sys, so that PagerCfg.exe overwrites the driver with log data and the operating system fails to boot.

Why it matters: The exploit needs no administrator rights and no zero-day: it waits on a routine action, an administrator sending a test SMS or AlarmWorX MMX firing an automatic alert, and leaves the SCADA host stuck in failed repair mode. Iconics Suite runs industrial processes in automotive, energy and manufacturing, so a corrupted boot on one of those hosts is an availability incident, not an IT ticket.

Read the original at Unit 42 Palo Alto Networks ↗

Topics
Vulnerabilities & Patching
Mentions
CVE-2024-7587CVE-2025-0921
Related